KYN28(A)-12 Type Armored Withdrawable AC Metal-Enclosed Switchgear
- Product Description
-
Product Overview
The KYN28(A)-12(GZS1)-type armored, withdrawable AC metal-clad switchgear (hereinafter referred to as "switchgear") is designed for use in three-phase 50Hz AC power systems, where it serves to receive and distribute electrical energy while also enabling circuit control, protection, and monitoring. Additionally, the newly introduced and developed high-current, high-breaking-capacity switchgear can be used independently at the outlet of high-voltage generators.
This product complies with the following standards: GB3906 "3~35kV AC Metal-Enclosed Switchgear," GB/T11022 "Common Technical Requirements for High-Voltage Switchgear and Control Equipment," and IEC298 "AC Metal-Enclosed Switchgear and Control Equipment Rated 1kV and Above up to 52kV."
Environmental operating conditions
Ambient air temperature: maximum +40°C, minimum -15°C.
Humidity conditions: Daily average relative humidity: <95%, with daily average water vapor pressure not exceeding 2.2 kPa; monthly average relative humidity: <90%, with monthly average water vapor pressure not exceeding 1.8 kPa.
Altitude: 2,500 m and below.
Seismic intensity: Not exceeding magnitude 8.
The surrounding air should be free from obvious contamination by corrosive or flammable gases, water vapor, and the like.
No locations with frequent, intense vibrations.
Use beyond the normal conditions specified by GB3906 requires consultation between the user and the manufacturer.
Ordering Instructions (Please specify when placing your order)
1. Main circuit scheme number, purpose, single-line system diagram, arrangement drawing, and distribution room layout plan, etc.
2. Schematic diagram of the auxiliary circuit wiring and terminal arrangement diagram.
3. Model, specifications, and quantity of electrical components within the switchgear.
4. Requirements for control, measurement, and protection functions of switching equipment, as well as requirements for other interlocking and automatic devices.
5. If bus bridges are required to connect switchgear units or incoming feeder cabinets, please provide specific data such as the rated current-carrying capacity of the bus bridge, its span length, and the height from the ground.
6. When attachments or spare parts are needed, please specify the type and quantity required.
7. If switchgear is to be used in special environmental conditions, please provide detailed specifications when placing your order.

Main Technical Specifications
Project Unit Data Rated power supply kV 3.6, 7.2, 12 Rated frequency Hz 50 Circuit breaker rated current A 630, 1250, 1600, 2000, 2500, 3150, 4000 Switchgear rated current A 630, 1250, 1600, 2000, 2500, 3150, 4000 Rated short-time withstand current (4s) kA 16, 20, 25, 31.5, 40, 50 Rated Peak Withstand Current (Peak) kA 40, 50, 63, 80, 100, 125 Rated Short-Circuit Interrupting Current kA 16, 20, 25, 31.5, 40, 50 Rated Short-Circuit Making Current (Peak) kA 40, 50, 63, 80, 100, 125 Rated
Insulation Level1-minute power frequency withstand voltage Between poles, between pole and ground kV 24, 32, 42 Between fracture surfaces kV 24, 32, 48 Lightning Impulse Withstand Voltage (Peak) Extreme-to-extreme, squeeze-to-ground kV 40, 60, 75 Between fracture surfaces kV 46, 70, 85 Protection Level The enclosure is rated IP4X, while the compartment and circuit breaker room remain at IP2X when their doors are open. Note: 1. The short-circuit capacity of the current transformer should be considered separately.
2. Altitude 1000m model, rated current ≤1250A, rated short-circuit breaking current <31.5kA.Structural Features
1. Switchgear Structure (see the figure below)
2. All-metal assembly with a modular, prefabricated structure.
3. The cabinet body is made from imported aluminum-zinc coated thin steel sheets, processed using an FMS flexible manufacturing system. It features advanced multi-fold edge technology and is assembled with self-clinching rivet nuts and high-strength bolts, ensuring high precision, excellent corrosion resistance, lightweight construction, superior strength, and exceptional versatility.
4. Equipped with either the ZN63A-12(VS1) series or the imported IVD4 series vacuum circuit breakers, offering wide applicability, high reliability, and maintenance-free operation.
5. The handcart features working and test positions, each equipped with positioning and display mechanisms that ensure safety and reliability.
6. Vehicles of the same specifications can be freely interchanged, offering high interchangeability.
7. The handcart is transported by a dedicated carrier vehicle, making operation convenient and flexible.
8. The cable room can accommodate up to 9 single-core cables.
9. Reliable mechanical and electrical interlocking devices that fully meet the "Five-Prevention" requirements.
10. Each high-voltage room is equipped with a pressure relief channel to ensure personal safety.
11. The front panel is equipped with an observation window, allowing you to monitor the operational status of internal components.
Schematic Diagram of Switchgear Structure
A. Busbar Chamber; B. Circuit Breaker Drawer Chamber; C. Cable Chamber; D. Relay and Instrument Chamber;
1. Enclosure; 2. Branch Busbar; 3. Busbar Bushing; 4. Main Busbar; 5. Static Contact Assembly; 6. Contact Box; 7. Current Transformer; 8. Earthing Switch; 9. Cables; 10. Surge Arrester; 11. Earthing Busbar; 12. Removable Partition; 13. Partition (Valve); 14. Secondary Plug; 15. Circuit Breaker Drawer; 16. Heating Device; 17. Withdrawable Horizontal Partition; 18. Earthing Switch Operating Mechanism; 19. Base Plate; 20. Pressure Relief Device; 21. Control Wire Channel External dimensions

(mm)
Height B 2300 (2200) Height A Rated current reaches 1250A 800 Rated current of 1600 A and above (rated current of 1250 A at an altitude of 4000 m) 1000 Deep C Cable entry and exit 1500 Overhead incoming and outgoing lines 1560 Installation dimensions

(mm)
Cabinet width A Cabinet Depth B L1 L2 L3 L4 800 1500 Cable 530 630 150 490 1660 feet in the air 530 630 310 650 1000 1500 Cable 730 830 150 490 1660 feet in the air 730 830 310 650
Contact us