For the isolating switch, models include series such as HD11F and others.
Shijiazhuang Mingshuo Electric Power Technology Co., Ltd.
Contact us
Service: 400-116-5838
WhatsApp:86-18532175010
Email:roger@msdlkj.com
No. 1 Ganjiang Road, Shijiazhuang Economic and Technological Development Zone, Shijiazhuang City, Hebei Province
JP Series Integrated Distribution Box (Compensation, Control, and Terminal Lighting)
- Product Description
-
Product Overview
The JP series outdoor integrated distribution box combines multiple functions—such as metering, outgoing circuits, and reactive power compensation—into a single, compact outdoor-ready device. It features advanced protection capabilities against short circuits, overloads, overvoltage, and leakage currents. With its small footprint, sleek design, and cost-effectiveness, this innovative product is ideally suited for installation on utility poles alongside outdoor-mounted transformers. It represents the next-generation ideal solution for upgrading power grids in both urban and rural areas.
Environmental operating conditions
● Ambient temperature: -25°C to +40°C.
● Relative air humidity: The daily average should not exceed 90%, and the monthly average should also remain below 90%.
● Altitude: Not exceeding 2500 m.
● Install in locations free from severe vibrations, shocks, and corrosive gases.
Structural Features
The enclosure structure comes in two types: upright and horizontal. The outer shell is crafted from 2mm-thick, high-quality stainless steel sheets, precisely bent using a multi-step edging process (or alternatively, a honeycomb-structured, stainless steel double-layer composite panel that offers flame-retardant, eco-friendly insulation, and anti-condensation properties). The enclosure is assembled using a specialized stainless steel welding technique, ensuring exceptional overall strength once formed, with a mirror-smooth, flawless surface free of any weld marks. Inside, the mounting beams (or panels) are treated with a hot-dip galvanizing process, guaranteeing corrosion resistance for at least 20 years. The enclosure features front and rear hinged doors for easy user access and maintenance. Each door is fitted with a highly elastic, age-resistant sealing strip around its perimeter, providing superior weatherproofing and protection against contaminants. Additionally, every door is equipped with both visible and concealed locking mechanisms; the visible lock includes an integrated rain shield designed to prevent blockages and rust buildup. The metering chamber is fully enclosed and secured with a lead-sealing mechanism. On the side of the enclosure, there’s a cable entry system featuring weatherproof, debris-resistant conduits, while the base incorporates strategically placed ventilation holes along with dedicated cable exit ports. At the top, a built-in ventilation channel paired with a fine-mesh screen ensures optimal airflow while effectively blocking dust, moisture, and foreign objects. Overall, the enclosure meets the stringent IP54 protection rating, offering robust defense against water splashes, dust, and external contaminants.
Ordering Instructions (Please specify when placing your order)
1. Product model and quantity.
2. Product structural type (vertical, horizontal).
3. Model numbers and technical specifications of the key components.
4. Other special requirements.
Structural Features
Serial Number Name Unit Parameters 1 Transformer Capacity KVA 30–400 2 Rated Operating Voltage V AC400 3 Auxiliary circuit operating voltage V AC220, AC380 4 Rated frequency Hz 50 5 Rated current A ≤630 6 Rated residual operating current mA 30–300 adjustable 7 Protection Level IP54 Compensation circuit options range from 1 to 4 circuits, with each circuit capable of handling 3 to 20 kVAR.
Additionally, a temperature and humidity control device can be optionally installed inside the box, depending on user requirements.
Main Circuit Diagram
Scheme Number 01 02 03 04 05 Main Circuit Single-Line Diagram 




Explanation Total Metering / Single Outgoing Feeder / Residual Current Protection Total Metering / Total Leakage Protection / Dual Circuit Output Total Metering / Total Leakage Protection / Three-Circuit Outlets Total Metering / Dual Outfeed / Branch Residual Current Protection Total Metering / Three-Phase Outlets / Branch Residual Current Protection Scheme Number 06 07 08 09 10 Main Circuit Single-Line Diagram 




Explanation Total Metering / Single-Circuit Output / Leakage Protection with Compensation Total Metering / Total Leakage Protection / Dual Circuit Output / With Compensation Total Metering / Total Leakage Protection / Three-Phase Outfeed / With Compensation Total Metering / Dual Outfeed / Branch Residual Current Protection / With Compensation Total Metering / Three-Phase Outlets / Branch Circuit Breakers with Compensation Box external dimensions
Bedroom cabinet external dimensions
Transformer Capacity Scheme Number L W H 30–100 kVA 01, 06 800 450 700 30–250 kVA 02, 04, 07, 09 900 500 700 100–400 kVA 03, 05, 08, 10 1100 600 800 Vertical cabinet external dimensions
Transformer Capacity Scheme Number L W H 30–100 kVA 01, 06 600 450 1000 30–250 kVA 02, 04, 07, 09 700 500 1000 100–400 kVA 03, 05, 08, 10 800 600 1100 *The above dimensions are for reference only.